Gasboy SiteOmat Maintenance Manual User Manual
Page 148

144
SiteOmat Setup and Maintenance Manual – MDE 4817G
7-7.5. Auto Calibration
The Auto Calibration process provides with an accurate strapping table giving the volume for
different levels in the actual tank structure.
The process utilizes the combined pump data and probe level to build a strapping table, based on
samples taken over time, in cycles between deliveries.
It is recommended to perform Auto Calibration at setup, and once every six months thereafter.
To start the Auto Calibration, proceed as follows:
1. Click on the Status navigation button
2. Select the Tanks tab. The Tank Status screen appears (see Figure 7-15)
Figure 7-15. Tank Status Screen
3. Click on the required tank indicator. The Auto Calibration Data dialog box appears (see
Figure 7-16)