Power Requirements

A separate line disconnect switch should be provided for each MAX200 power supply. The disconnect box should
be sized to the following requirements:

Rated Input

Input

Current @

Recommended

Voltage

Phase

30 kw Output

Fuse Size

200 VAC

3

108 amps

150 amps

208 VAC

3

104 amps

150 amps

220 VAC

3

98 amps

150 amps

380 VAC

3

57 amps

80 amps

400 VAC

3

56 amps

80 amps

415 VAC

3

52 amps

70 amps

480 VAC

3

45 amps

60 amps

600 VAC

3

36 amps

50 amps

Line Disconnect Switch

• Use a primary line disconnect switch for each power supply. This disconnect switch allows you to turn the

power supply off quickly in an emergency situation. The switch should be located on a wall near the power
supply, and should be easily accessible to the operator. The interrupt level of the switch must be equal to or
exceed the continuous rating of the fuses. Refer to Power Requirements listed above.

Power Cables

• Use AWG wire sizes as outlined by applicable local electrical codes. Wire sizes vary based on the distance

of the receptacle from the main box.

• Use a 4-conductor Type SO input power cable with a conductor temperature rating of 60°C (140°F)

according to the following requirements:

Input Voltage

Cable Size

Current Rating

200 VAC

1/4

107 amps

208 VAC

1/4

107 amps

220 VAC

1/4

107 amps

380 VAC

4/4

69 amps

400 VAC

4/4

69 amps

415 VAC

4/4

69 amps

480 VAC

6/4

52 amps

600 VAC

8/4

39 amp