12  Parameters

SMA Solar Technology AG

100

SCCP-JP-BA-A4-en-12

User Manual

12.1.3 Grid Support

Name

Description

Value/range Explanation

Default value

FRT2ArGraNomHi*

Slope of the FRT characteristic

curve in accordance with the

System Service Ordinance

SDLWindV in case of overvoltage

0 to 10

Values between

0 and 2 are

recommended.

For other values,

contact the SMA

Service Line.

2

FRT2ArGraNomLo*

Slope of the FRT characteristic

curve in accordance with the

System Service Ordinance

SDLWindV in case of undervoltage

0 to 10

2

FRTArGraNom*

Scaling of K factor for full dynamic

grid support

0 to 10

2

FRTDbVolNomMax**

Upper limit of voltage deadband

0% to 100%

10%

FRTDbVolNomMin**

Lower limit of voltage deadband

− 100% to 0% ‒

− 10%

FRTEna*

* To view or change this parameter, you must enter the installer password.

Enables dynamic grid support

Off

Deactivated

On

On

Activated

FRTMod**

** You can only view this parameter after entering the installer password.

Dynamic grid support mode

FRT_BDEW

Dynamic grid

support in

accordance with

BDEW directives

FRT_SDLWindV

FRT_Partial

Pulse block in the

event of FRT

FRT_SDLWindV Dynamic grid

support in

accordance with

SDLWindV

FRTSwOffTm**

Deactivation delay for dynamic

grid support

0 ms to 1,000

ms

500 ms

EnaAid*

Enables islanding detection

Off

Deactivated

On

On

Activated

TrfVolExlHi***

*** To change this parameter, you must enter the installer password.

Line-to-line voltage on overvoltage

side of external transformer

1 V to

70,000 V

20,000 V

TrfVolExlLo***

Line-to-line voltage on undervoltage

side of external transformer

1 V to 500 V

SC 500CP-JP

205 V

SC 630CP-JP

315 V

SC 800CP-JP

360 V