2 no active power limitation: off mode – SMA SC 500CP-10-JP User Manual

Page 51

Advertising
background image

SMA Solar Technology AG

8  Power Control

User Manual

SCCP-JP-BA-A4-en-12

51

5. Use the parameter PwrMonErrMod to select the desired inverter behavior in the absence of setpoint specifications

as follows:

6. If SubVal has been selected, enter the proxy values for normal feed-in operation and for operation outside of normal

feed-in operation, as follows:

7. In the parameter PwrMonErrTm configure the time lapse until recognition of the absence of setpoint specifications.
8. Confirm the parameter entry with [Save].

8.1.2.2 No Active Power Limitation: Off Mode

The feed-in power is limited to the parameter Pmax.
The parameter Pmax defines the Sunny Central power at the feed-in point and is adjusted to the local conditions during

commissioning. The parameter Pmax can only be changed when the device is in the operating state "Stop" and the

installer password has been entered.

8.1.2.3 Active Power Limitation with Setpoint Command via Modbus Protocol: WCtlCom

Mode

The setpoint for active power limitation is received by the Sunny Central via the Power Reducer Box or the Power Plant

Controller and then transmitted to the Sunny Central. If the Sunny Central has not received any signal for five minutes,

the error message will be displayed in the instantaneous value P-WModFailStt.

8.1.2.4 Active Power Limitation with Absolute Value: WCnst Mode

The active power limitation is entered as an absolute value via the parameter P-W.
The parameter P-W defines the active power to be fed in. The parameter P-W can be changed in feed-in operation. The

parameter P-W must not be greater than the parameter Pmax.

8.1.2.5 Active Power Limitation as a Percentage of Nominal Power: VArCnstNom Mode

The active power limitation is set as a percentage value via the parameter P-WNom. The percentage value refers to the

parameter Pmax.
The parameter P-WNom indicates what percentage of the maximum possible power is to be fed in. The parameter

P-WNom can be changed during feed-in operation.

Setting

Description

LastVal

If specified via communication: utilization of the last value received. In case of analog

setpoints: utilization of the last valid mean value.

SubVal

Utilization of the configured proxy values. SMA recommends use of the proxy values when

setpoint specifications are effected via analog signals.

Parameters

Description

P-WSubValRun

Proxy value for active power limitation in feed-in operation

P-WSubVal

Proxy value for active power limitation outside of feed-in operation