SMA SC 500CP-10-JP User Manual

Page 55

Advertising
background image

SMA Solar Technology AG

8  Power Control

User Manual

SCCP-JP-BA-A4-en-12

55

8.2.1.3 Reactive Power Control with Setpoint Command via Modbus Protocol:

VArCtlCom Mode

The reactive power setpoint is received by the Sunny Central via the Power Reducer Box or the Power Plant Controller.

The setpoint is transmitted as a percentage and converted to kVAr in the device.
If the Sunny Central has not received any signal for the last five minutes, the error message Q-VArModFailStt will be

displayed (see Section 8.2.2, page 63).

8.2.1.4 Reactive Power Control with Setpoint Command via Modbus Protocol: PFCtlCom

Mode

The reactive power setpoint is received by the Sunny Central via the Power Reducer Box or the Power Plant Controller.

The setpoint is transmitted as a displacement power factor cos φ.
If the Sunny Central has not received any signal for the last five minutes, an error message will be displayed in the

instantaneous value Q-VArModFailStt (see Section 8.2.2, page 63).

8.2.1.5 Reactive Power Control with Absolute Value: VArCnst Mode

The Q-VAr parameter is used to set the reactive power setpoint. The permitted range of the parameter Q-VAr is between

‒Qmax and +Qmax.

8.2.1.6 Reactive Power Control as a Percentage of the Nominal Power: VArCnstNom

Mode

The parameter Q-VArNom is used to set the reactive power setpoint in %. The parameter Q-VArNom refers to Pmax.

If the calculated amount of reactive power exceeds the predefined value of Qmax, the power will be limited to Qmax.

If the calculated amount of reactive power falls below the predefined value of ‒Qmax, the power will be limited to

‒Qmax.

8.2.1.7 Reactive Power Setpoint via Standard Signal: VArCnstNomAnIn Mode

The reactive power setpoint is set via an analog signal at the input terminals for setpoint specification (see Sunny Central

installation manual). This is usually implemented by a ripple control signal.
The analog value is converted into a reactive power setpoint. The electrical current strength of the connected signal

determines the setpoint.
The analog measured values must be between 4 mA and 19 mA. If the analog signal is less than 2 mA, an error message

will be displayed in the instantaneous value Q-VArModFailStt (see Section 8.2.2, page 63).

The analog value is converted to a setpoint for power limitation. Here, the Qmax parameter forms the end point of the

linear characteristic curve.

Signal

Power limit

Description

< 2 mA

Last valid mean value or

0 kVAr after restart

Signal is in the invalid range.

2 mA to 4 mA

− Pmax

The maximum amount of negatively excited reactive power is fed in.

4 mA

− Pmax

Start point of the characteristic curve
The maximum amount of negatively excited reactive power is fed in.

11.5 mA

0 kVAr

Zero-crossing of the characteristic curve
No reactive power is fed in.

> 19 mA

+Pmax

End point of the characteristic curve
The maximum amount of positively excited reactive power is fed in.

Advertising