8.2 Reactive Power Control

8.2.1 Mode of Reactive Power Control

8.2.1.1 Selecting the Mode with the Parameter Q-VArMod

The Sunny Central can supply reactive power if required by the grid operator. The grid operator specifies the modes and

setpoints to be used.
You can set the mode of reactive power control via the parameter Q-VArMod. Use this parameter to configure how the

specifications of the grid operator are to be received and implemented.
There are eleven different modes of reactive power control. The default value for this parameter is Off.
If a displacement power factor cos φ of 1 is to be permanently complied with, SMA Solar Technology AG recommends

using the PFCnst mode.

ComFail

The WCtlCom mode has been selected and the expected signal with a valid active power limit has

been absent for at least five minutes.

Corrective measures:

• Ensure that the Sunny Central and the Power Reducer Box or Power Plant Controller can be

accessed via the Internet.

• Ensure that the Sunny Central and the Power Reducer Box or the Power Plant Controller are

connected correctly.

• Ensure that the cabling between the Sunny Central and Power Reducer Box or the Power Plant

Controller is OK.

AnInFail

The WCnstNomAnIn mode has been selected and the value measured at the analog input is less

than 2 mA.

Corrective measures:

• Make sure the signal cable is correctly connected to the analog input.

ComInvalid The WCtlCom procedure has been selected and there is invalid content in the power setpoint data.

Corrective measures:

• Ensure that the settings for the power setpoints are correct.

Mode

Description

Off

The reactive power setpoint is limited to 0 kVAr.

VArCtlCom

The reactive power setpoint is received by the SC-COM via the Power Reducer Box or Power Plant

Controller and then transmitted to the Sunny Central.

PFCtlCom

The reactive power setpoint is received by the SC-COM via the Power Reducer Box or Power Plant

Controller and then transmitted to the Sunny Central. A displacement power factor cos φ is

transmitted as the setpoint.

VArCnst

The parameter Q-VAr is used to set the reactive power setpoint in kVAr.

VArCnstNom

The parameter Q-VArNom is used to set the reactive power setpoint in % relative to Pmax.

VArCnstNomAnIn The reactive power setpoint is imported via an analog input. The analog value is converted into a

reactive power setpoint.

PFCnst

The reactive power setpoint is set via a displacement power factor cos φ.

Display

Cause and corrective measure