12  Parameters

User Manual

SCCP-JP-BA-A4-en-12

91

P-WGra**

Gradient of power

reduction

1%/Hz to 100%/Hz

40%/Hz

PFAbsMin*

Limitation of the

displacement power

factor cos φ

0.5 to 1

The parameter should not

fall below 0.8 in normal

operation.

0.9

PF-PF

Displacement power

factor cos φ
The lower limit is

defined by the

parameter PFAbsMin.

0.5 to 1

The parameter should not

fall below 0.8 in normal

operation.

1

PF-PFExt

Excitation of the

displacement power

factor cos φ

OvExt

Lagging

OvExt

UnExt

Leading

PF-PFStr**

Displacement power

factor cos φ at

characteristic curve

point 1
The lower limit is

defined by the

parameter PFAbsMin.

0.5 to 1

The parameter should not

fall below 0.8 in normal

operation.

0.9

PF-PFExtStr**

Excitation of the

displacement power

factor cos φ at

characteristic curve

point 1

OvExt

Lagging

OvExt

UnExt

Leading

PF-PFStop**

Displacement power

factor cos φ at

characteristic curve

point 2
The lower limit is

defined by the

parameter PFAbsMin.

0.5 to 1

The parameter should not

fall below 0.8 in normal

operation.

0.9

PF-PFExtStop**

Excitation of the

displacement power

factor cos φ at

characteristic curve

point 2

OvExt

Lagging

OvExt

UnExt

Leading

PF-WStr**

Specification of feed-in

power in % at

characteristic curve

point 1

0% to 90%

0%

PF-WStop**

Specification of feed-in

power in % at

characteristic curve

point 2

10% to 100%

100%

Name

Description

Value/range

Explanation

Default

value