2 no reactive power control: off mode – SMA SC 500CP-10-JP User Manual

Page 54

Advertising
background image

8  Power Control

SMA Solar Technology AG

54

SCCP-JP-BA-A4-en-12

User Manual

Procedure:

1. Ensure that the Sunny Central is in the operating state "Stop".
2. Log into the user interface.
3. Change the parameter Q-VarMod (see Section 6.2, page 40).
4. Change any parameters associated with the selected mode.
5. Use the parameter PwrMonErrMod to select the desired inverter behavior in the absence of setpoint specifications

as follows:

6. If SubVal has been selected, enter the proxy values for normal feed-in operation and for operation outside of normal

feed-in operation, as follows:

7. In the parameter PwrMonErrTm configure the time lapse until recognition of the absence of setpoint specifications.
8. Confirm the parameter entry with [Save].

8.2.1.2 No Reactive Power Control: Off Mode

The reactive power setpoint is limited to 0 kVAr. This setpoint cannot be controlled.

PFCnstAnIn

The reactive power setpoint is imported via the analog input for setpoint specification. The analog

value is converted into a displacement power factor cos φ.

PFCtlW

The displacement power factor cos φ is set as a function of the feed-in power. The dependency is

depicted by a configurable characteristic curve.

VArCtlVol

The reactive power is set as a function of the line voltage.

VArCtlVolHystDb

The provision of reactive power helps perform voltage-stabilizing measures in the event of

overvoltage or undervoltage. The parameterization is carried out by means of a reactive

power/voltage characteristic curve.

VArCtlVolHysDbA The provision of reactive power helps perform voltage-stabilizing measures in the event of

overvoltage or undervoltage. The parameterization is carried out by means of a reactive

power/voltage characteristic curve and an activation power.

Parameter block
The parameter Q-VARMod can only be changed in the operating state "Stop". The entry will not be accepted in

any other operating state.

Setting

Description

LastVal

If specified via communication: utilization of the last value received. In case of analog

setpoints: utilization of the last valid mean value.

SubVal

Utilization of the configured proxy values. SMA recommends use of the proxy values when

setpoint specifications are effected via analog signals.

Parameters

Description

Q-VArSubValRun

Proxy value for the reactive power setpoint in feed-in operation

PF-PFSubValRun

Proxy value for the displacement power factor in feed-in operation

PF-PFExtSubValR

Proxy value for the excitation of the displacement power factor in feed-in operation

Q-VArSubVal

Proxy value for the reactive power setpoint outside of feed-in operation

PF-PFSubVal

Proxy value for the displacement power factor outside of feed-in operation

PF-PFExtSubVal

Proxy value for the excitation of the displacement power factor outside of feed-in operation

Mode

Description

Advertising