3  Product Description

SMA Solar Technology AG

30

SCCP-JP-BA-A4-en-12

User Manual

The dynamic grid support function is configured via the parameter FRTEna. The level of reactive current provided with

full dynamic grid support is determined via the parameter FRTArGraNom.
For the order option "Q at Night", limited dynamic grid support is available in the operating state "Q at Night".

3.8.6 Decoupling Protection Ramp

After a grid fault, the Sunny Central restarts at a maximum of 10% nominal power per minute using a decoupling

protection ramp. You have the option of switching this decoupling protection ramp on or off. If you deactivate the

decoupling protection ramp, the Sunny Central rapidly reverts to maximum power. If you wish to deactivate the

decoupling protection ramp, contact the SMA Service Line.

3.8.7 Grid Management Shutdown

If the utility grid becomes unstable, grid management requires that the Sunny Central disconnects from the utility grid

immediately to avoid grid overload. In this event a corresponding Modbus signal will be provided by the grid operator

or the safety system at the grid transfer point. The Sunny Central disconnects from the utility grid immediately and displays

the error 9013. The error will be reset in the Sunny Central after a signal from the grid operator or the safety system for

the grid transfer point.

Ratio V

Grid

/V

Behavior of the Sunny Central

90% to 100%

The ratio of line voltage V

Grid

to nominal voltage V is in the normal range and the Sunny Central

feeds in without any problem.

20% to 90%

The ratio of line voltage V

Grid

to nominal voltage V is in the critical range. There is a disturbance

in the utility grid. While this error is present, the Sunny Central supports the utility grid with reactive

current. The Sunny Central can bridge errors of up to 5 s without disconnecting from the utility grid.

If the configured grid monitoring time is exceeded during this period, the Sunny Central

disconnects from the utility grid.

0% to 20%

The ratio of line voltage V

Grid

to nominal voltage V is in the critical range. There is a disturbance

in the utility grid. While this disturbance is present, the Sunny Central supports the utility grid with

reactive current. The Sunny Central can bridge disturbances of up to 1.2 s without disconnecting

from the utility grid. This is provided that the V

Grid

/V ratio was >= 90% before the fault occurred.

If the set grid monitoring time is exceeded during this period, the Sunny Central disconnects from

the utility grid.

Compliance with the Medium-Voltage Directive
The decoupling protection ramp is part of the Medium-Voltage Directive of the German Association of Energy and

Water Industries (BDEW) and must not be deactivated in Germany.