12  Parameters

SMA Solar Technology AG

92

SCCP-JP-BA-A4-en-12

User Manual

P-VtgGraNom

Active power gradient

for voltage-dependent

active power limitation

0.017%/s to

100.000%/s

0.166%/s

P-VtgEna

Activation of

voltage-dependent

active power limitation

Off

Deactivated

Off

On

Activated

P-VtgNomP1

Voltage at point 1

100% to 120%

110%

P-VtgNomP2

Voltage at point 2

90% to 120%

100%

P-VtgAtMin

Minimum active power

for voltage-dependent

active power limitation

0% to 100%

20%

PwrApLimitPrio*** Prioritization of reactive

power or active power

PrioPwrRt

Prioritization of reactive

power

PrioPwrRt

PrioPwrAt

Prioritization of active

power

P-WSubVal

Proxy value for active

power limitation outside

of normal feed-in

operation in the event of

communication failure

0 kW to 1,000 kW

SC 500CP-JP

500 kW

SC 630CP-JP

700 kW

SC 800CP-JP

880 kW

PF-PFSubVal

Proxy value for cos φ

outside of normal

feed-in operation in the

event of communication

failure

0.5 to 1

The value 0.5 cannot be

reached in normal

operation.

1

PF-PFExtSubVal

Proxy value for

excitation type in the

event of communication

disturbance

OvExt

Lagging

OvExt

UnExt

Leading

P-WSubValRun

Proxy value for the

active power limitation

during feed-in operation

in the event of

communication

disturbance

0 kW to 1,000 kW

SC 500CP-JP

500 kW

SC 630CP-JP

700 kW

SC 800CP-JP

880 kW

PF-PFSubValRun

Proxy value cos φ in

normal feed-in

operation in the event of

communication

disturbance

0.5 to 1

The parameter should not

fall below 0.8 in normal

operation.

1

PF-PFExtSubValR

Proxy value of the

excitation type during

normal feed-in

operation in the event of

communication

disturbance

OvExt

Lagging

OvExt

UnExt

Leading

Name

Description

Value/range

Explanation

Default

value