12  Parameters

User Manual

SCCP-JP-BA-A4-en-12

97

Q-VAr

Reactive power in kVAr − 220 kVAr to +220 kVAr SC 500CP-JP

0 kVAr

− 310 kVAr to +310 kVAr SC 630CP-JP
− 385 kVAr to +385 kVAr SC 800CP-JP

QoDQ-Var**

Reactive power in kVAr

in the operating state

"Q at Night"

− 500 kVAr to +500 kVAr SC 500CP-JP

0 kVAr

− 700 kVAr to +700 kVAr SC 630CP-JP
− 880 kVAr to +880 kVAr SC 800CP-JP

Q-VArNom

Reactive power in %

− 100% to 100%

0%

QoDQ-VArNom

Reactive power in % in

the operating state

"Q at Night"

− 100% to 100%

0%

QoDEna*

Activates/deactivates

the function

"Q at Night"

Off

Deactivated

Off

On

Activated

QoDDccOffDelay* Delay time until the DC

switchgear opens in the

operating state

"Q at Night"

0 s to 86,400 s

3,600 s

SDLimComSrc***

Selection of the

SDELimit source

CAN

SC-COM interface

UART

UART

Via SMA Net

WCtlHzMod**

Activation of

frequency-dependent

active power limitation

Off

Deactivated

Off

CurveHys

Procedure with hysteresis

Curve

Procedure without

hysteresis

WGra**

Active power change

gradient

1% to 100%

100%

WGraEna**

Activation of the active

power change gradient

Off

Deactivated

On

On

Activated

WGraRecon**

Active power change

gradient after a grid

error

0.017%/s to 100.00%/s ‒

0.166%/s

WGraReconEna** Activation of the

decoupling protection

ramp for reconnection

Off

Deactivated

Off

On

Activated

* This parameter can only be viewed.

** To change this parameter, you must enter the installer password.

*** To view or change this parameter, you must enter the installer password.