10.4.3 Error Numbers 01xx to 13xx - Disturbance on the Utility Grid

After a grid failure, the Sunny Central monitors the utility grid for a certain time before reconnecting.
When the Sunny Central monitors the utility grid after a grid error, the grid monitoring time is maintained.
Certain grid errors cause the Sunny Central to shut down. In this case, the instantaneous value TmsRmg indicates the

time for which the Sunny Central monitors the utility grid before reconnecting. This grid monitoring time after a grid error

can be defined in parameter GdErrTm.
You can prevent automatic reconnection of the Sunny Central after a grid error has occurred by setting the parameters

(see Section 8 "Power Control", page 49). Only after acknowledgement of the error will the Sunny Central switch on

again.

Error no.

Explanation

Behavior of the

Sunny Central

Corrective measures

S 1

S 2

R

0103*

Line voltage is too high.

Overvoltage detected by

redundant monitoring.

30 s

30 s

• Check line voltage.
• Check grid connections.
• Check stability of the utility

grid.

• Make sure the external fuses

function properly.

• Make sure the AC cable

connections are securely

connected.

0104*

Line voltage is too high.

Overvoltage detected by standard

monitoring.

C

C

0203*

Line voltage is too low.

Undervoltage detected by

redundant monitoring.

30 s

30 s

0204*

Line voltage is too low.

Undervoltage detected by standard

monitoring.

30 s

30 s

0205

One line conductor of the utility grid

has failed.

30 s

30 s

0502*

Power frequency is too low.

Power frequency fault detected by

standard monitoring.

30 s

30 s

• Check power frequency.
• Check the grid monitoring

relay display.

• Make sure the fuses in the load

circuit function properly.

0503*

Power frequency is too high.

Power frequency fault detected by

standard monitoring.

30 s

30 s

0504*

Power frequency is too low.

Power frequency fault detected by

redundant monitoring.

30 s

30 s

0505*

Power frequency is too high.

Power frequency fault detected by

redundant monitoring.

30 s

30 s

0506*

The Sunny Central has detected a

stand-alone grid and disconnected

from the utility grid.

W

W

• Check power frequency.