12  Parameters

SMA Solar Technology AG

94

SCCP-JP-BA-A4-en-12

User Manual

Q-VArGraNom

Neg**

Reactive power

gradient at a negative

change of nominal

voltage

0%/V to 44.06%/V

SC 500CP-JP

0%/V

0%/V to 31.47%/V

SC 630CP-JP

0%/V to 25.04%/V

SC 800CP-JP

Q-VArMod**

Specification of the

reactive power setpoint

mode

Off

Sets reactive power to

0 kVAr and displacement

power factor cos φ to 1

Off

VArCtlCom

Specification of reactive

power via external control

unit, such as the Power

Reducer Box

PFCtlCom

Specification of

displacement power factor

cos φ and excitation of the

displacement power factor

via an external control unit

such as the Power Reducer

Box

VArCnst

Specification of reactive

power in kVAr via the

parameter Q-VAr

VArCnstNom

Specification of reactive

power in % via the

parameter Q-VArNom

VArCnstNomAnIn

The reactive power setpoint

is imported via an analog

input.

PFCnst

Manual specification of

displacement power factor

cos φ and excitation of the

displacement power factor

via the parameters PF-PF

and PF-PFExt

PFCnstAnIn

Specification of

displacement power factor

cos φ at the analog input

QExlSpnt via control unit

PFCtlW

Specification of

displacement power factor

cos φ as a function of the

feed-in power

VArCtlVol

Specification of reactive

power as a function of the

line voltage

Name

Description

Value/range

Explanation

Default

value