4 insulation monitoring, 5 internal device values – SMA SC 500CP-10-JP User Manual

Page 101

Advertising
background image

SMA Solar Technology AG

12  Parameters

User Manual

SCCP-JP-BA-A4-en-12

101

12.1.4 Insulation Monitoring

12.1.5 Internal Device Values

Name

Description

Value/range Explanation

Default

value

IsoErrIgn*

* To view or change this parameter, you must enter the installer password.

Enables insulation error

detection, continued operation

in the event of insulation error

Off

Deactivated

Off

On

Activated

Run

Error is only ignored if the

inverter is in feed-in operation

RemMntSvc

Deactivates PV array grounding.

Off

Deactivated

Off

On

Activated

RisoCtlWarn

Warning threshold for insulation

monitoring device iso-PV1685

0 kΩ to 50 kΩ ‒

45 kΩ

PvVtgRisoStart

Start voltage of insulation

measurement

0 V to 1,200 V SC 500CP-JP

410 V

SC 630CP-JP

610 V

SC 800CP-JP

760 V

PvVtgRisoDif

Differential voltage to

PvVtgStrLevMin for switching

from insulation measurement to

feed-in operation

− 250 V to

+250 V

0 V

IsoDev*

Selection of insulation

monitoring device

isoPV3

isoPV3

isoPV1685

Name

Description

Value/range Explanation

Default value

Ackn

Acknowledges errors in Sunny Central

Ackn

Acknowledge

errors

CardFunc*

MMC/SD memory card function

ForcedWrite

Terminate SD

memory card

StoFailHis

Write fault

memory to SD

memory card

CntRs*

Meter reset

h-Cnt

Operating hours

meter

E-Cnt

Energy meter

CntFanHs

All fan runtime

meters

CntFanCab2

Fan runtime meter

CntHtCab2

Fan runtime meter

CntrySet*

Selection of valid power frequency
This parameter can only be changed in

the operating state "Stop".

J50

For 50 Hz grid

J60

For 60 Hz grid