12  Parameters

User Manual

SCCP-JP-BA-A4-en-12

99

VCtlhhLim*

Threshold for overvoltage release

level 2

100% to 150%

130%

VCtlhhLimTm*

Tripping time for overvoltage

level 2

0 ms to

1,000,000 ms

100 s

VCtlhLim*

Threshold for overvoltage release

level 1

100% to 150%

110%

VCtlhLimTm*

Tripping time for overvoltage

level 1

0 ms to

1,000,000 ms

500 s

VCtllLim*

Threshold for undervoltage

release level 1

0% to 100%

80%

VCtllLimTm*

Tripping time for undervoltage

level 1

0 ms to

1,000,000 ms

1,000 s

VCtlllLim*

Threshold for undervoltage

release Level 2

0% to 100%

45%

VCtlllLimTm*

Tripping time for undervoltage

level 2

0 ms to

1,000,000 ms

300 s

VCtlMin*

Threshold for undervoltage

release level 3

0% to 100%

0

VCtlMinTm*

Tripping time for undervoltage

level 3

0 ms to

1,000,000 ms

0

VCtlPeakMax*

Threshold for overvoltage

120% to 150%

134%

VCtlPeakMaxTm*

Tripping time for overvoltage

0 ms to 20 ms

1 ms

VCtlOpMinNom*

Minimum connection voltage

0% to 100%

90%

VCtlOpMaxNom*

Maximum connection voltage

100% to 200%

110%

VRtg*

Nominal line voltage of the

utility grid

1 V to 70,000 V

20,000 V

ManResOvrVol*

Manual activation after

interruption due to overvoltage

Off

Deactivated

Off

On

Activated

ManResUndrVol*

Manual activation after

interruption due to undervoltage

Off

Deactivated

Off

On

Activated

ManResOvrFrq*

Manual activation after

interruption due to overfrequency

Off

Deactivated

Off

On

Activated

ManResUndrFrq*

Manual activation after

interruption due to underfrequency

Off

Deactivated

Off

On

Activated

ManResPID*

Manual activation after

interruption due to passive

islanding detection

Off

Deactivated

Off

On

Activated

ManResPLD*

Manual activation after

interruption due to disturbance in

a line conductor

Off

Deactivated

Off

On

Activated

* To change this parameter, you must enter the installer password.

Name

Description

Range

Explanation

Default value