12  Parameters

SMA Solar Technology AG

98

SCCP-JP-BA-A4-en-12

User Manual

12.1.2 Grid Monitoring/Grid Limits

Name

Description

Range

Explanation

Default value

HzCtlOpMin*

Minimum connection frequency

45 Hz to 50 Hz

For 50 Hz grid

49.5 Hz

55 Hz to 60 Hz

For 60 Hz grid

59.4 Hz

HzCtlOpMax*

Maximum connection frequency

50 Hz to 55 Hz

For 50 Hz grid

50.5 Hz

60 Hz to 65 Hz

For 60 Hz grid

60.6 Hz

HzCtlOpMaxRecon* Maximum connection frequency

after grid error

50 Hz to 55 Hz

For 50 Hz grid

50.5 Hz

60 Hz to 65 Hz

For 60 Hz grid

60.6 Hz

HzCtlMax*

Threshold for overfrequency

level 3

50 Hz to 55 Hz

For 50 Hz grid

0

60 Hz to 66 Hz

For 60 Hz grid

HzCtlMaxTm*

Tripping time for overfrequency

level 3

0 ms to

1,000,000 ms

0

HzCtlhhLim*

Threshold for overfrequency

level 2

50 Hz to 55 Hz

For 50 Hz grid

52 Hz

60 Hz to 66 Hz

For 60 Hz grid

62 Hz

HzCtlhhLimTm*

Tripping time for overfrequency

level 2

0 ms to

1,000,000 ms

600 ms

HzCtlhLim*

Threshold for overfrequency

level 1

50 Hz to 55 Hz

For 50 Hz grid

51 Hz

60 Hz to 66 Hz

For 60 Hz grid

61.2 Hz

HzCtlhLimTm*

Tripping time for overfrequency

level 1

0 ms to

1,000,000 ms

1,000 ms

HzCtllLim*

Threshold for underfrequency

level 1

45 Hz to 50 Hz

For 50 Hz grid

49 Hz

55 Hz to 60 Hz

For 60 Hz grid

58.8 Hz

HzCtllLimTm*

Tripping time for underfrequency

level 1

0 ms to

1,000,000 ms

1,000 ms

HzCtlllLim*

Threshold for underfrequency

level 2

45 Hz to 50 Hz

For 50 Hz grid

48 Hz

55 Hz to 60 Hz

For 60 Hz grid

58 Hz

HzCtlllLimTm*

Tripping time for underfrequency

level 2

0 ms to

1,000,000 ms

600 ms

HzCtlMin*

Threshold for underfrequency

level 3

45 Hz to 50 Hz

For 50 Hz grid

47 Hz

55 Hz to 60 Hz

For 60 Hz grid

57 Hz

HzCtlMinTm*

Tripping time for underfrequency

level 3

0 ms to

1,000,000 ms

600 ms

VCtlCharEna*

Activation of dynamic

undervoltage detection

Off

On

On

VCtlCharTm*

Start time of dynamic

undervoltage detection

0 ms to

1,000,000 ms

77 ms

VCtlMax*

Threshold for overvoltage release

level 3

100% to 150%

0

VCtlMaxTm*

Tripping time for overvoltage

level 3

0 ms to

1,000,000 ms

0