10  Troubleshooting

User Manual

SCCP-JP-BA-A4-en-12

83

7600

Communication between touch

display and SC-COM interrupted.
Error number appears on display

only.

W

W

• Check cabling between touch

display and SC-COM.

• Contact the SMA Service Line.

7601

Internal Sunny Central error.

30 s

1 min

x

• Contact the SMA Service Line.

7602

Internal communication error or

missing communication

30 s

1 min

x

7605

30 s

1 min

x

7704

Faulty switching status of DC

disconnection unit

30 s

Q

• When disconnecting the

Sunny Central from voltage

sources, check that all

motor-driven circuit breaker

switches are set to the OFF

position. If this is not the case,

set all switches to the OFF

position (see Sunny Central

installation manual).

• Contact the SMA Service Line.

7706

AC circuit breaker has tripped.

30 s

Q

• Contact the SMA Service Line.

7707

Faulty switching state of AC

contactor

30 s

Q

7708

Faulty switching state of Remote

GFDI

W

W

7709

90% of switch cycles of the DC

switchgear reached

10 s

10 s

7710

100% of switch cycles of the DC

switchgear reached

10 s

10 s

7714

Maximum number of GFDI switch

cycles reached

30 s

30 s

• Replace GFDI.

7801

Surge arrester defective.

W

W

• Check surge arrester.

7901

Reverse current has occurred in

PV array.

1 min

C

x

• Contact the SMA Service Line.

8701

External active power setpoints are

smaller than 2 mA and therefore

invalid.
The last valid value or, after a day

change, Pmax is used. Once valid

setpoints are available again, these

are used.

W

W

8702

Several digital active power

setpoints available.

W

W

8703

External power factor cos φ invalid

W

W

Error no.

Explanation

Behavior of the

Sunny Central

Corrective measures

S 1

S 2

R