SMA SC 500CP-10-JP User Manual

Page 57

Advertising
background image

SMA Solar Technology AG

8  Power Control

User Manual

SCCP-JP-BA-A4-en-12

57

The analog value is converted into a setpoint for the displacement power factor cos φ. Here, the parameter PFAbsMin

is the starting and end point of the linear characteristic curve.

8.2.1.10 Displacement Power Factor cos φ as a Function of Feed-In Power: PFCtlW Mode

With the PFCtlW mode, the displacement power factor cos φ is set as a function of feed-in power. The dependency is

depicted by a configurable characteristic curve. The characteristic curve can be configured as rising or falling. The start

and end points of the characteristic curve can be set via parameters.

Figure 20: Characteristic curve for reducing reactive power as a function of active power

On the basis of a linear characteristic curve with an upper and lower cap, a displacement power factor cos φ can be

regulated depending on the active power currently being fed in. The start and end points of the characteristic curve can

be configured by means of parameters. The shape of the characteristic curve is determined by the start and end points.

> 19 mA

PFAbsMin/overexcited End point of the characteristic curve

Maximum amount of positively excited reactive power is fed in.

Signal

Power limit

Description

Advertising