10  Troubleshooting

SMA Solar Technology AG

80

SCCP-JP-BA-A4-en-12

User Manual

3504

Insulation monitoring device has

detected an insulation error. Since

the parameter IsoErrIgn is set to

On, this error is ignored.

W

W

• Check PV array for ground

faults.

3507

Ground fault has occurred on

ungrounded pole of PV array.

Q

Q

3510

The Sunny Central has found an

insulation error on the inverter

bridge.

Q

Q

3511

The Sunny Central has found an

insulation error.

W

W

3512

The Remote GFDI has detected a

permanent ground fault.

Q

Q

3515

A ground fault detected by Soft

Grounding has been ignored.

W

W

3601

Leakage current to ground is

present in the PV array, or the

threshold defined in parameter

RisoCtlWarn has been reached.

W

W

• Check grounding and

equipotential bonding.

• Check module wiring and

PV system design.

• Check the RisoCtlWarn

parameter.

3803

Current of PV array is too high.

1 min

D

x

• Check DC input current.
• Check module wiring and

PV system design.

4000

String-failure detection has detected

a defective string. Error number

appears on display only.

W

W

• Read off the number of the

defective string in the

instantaneous value

SSMUWrnCode.

4003

Reverse currents detected in the

PV array, or DC terminal

reverse-poled.

30 s

Q

• Check PV modules for short

circuits.

• Check module wiring and

PV system design.

• Check DC terminals for correct

polarity.

• Check the functionality of the

entire string.

4004

String-current monitoring has

detected a defective string.

W

W

-

• Check the functionality of the

entire string.

Error no.

Explanation

Behavior of the

Sunny Central

Corrective measures

S 1

S 2

R