3  Product Description

User Manual

SCCP-JP-BA-A4-en-12

27

Insulation Monitoring

To disable the grounding of the PV array, the RemMntSvc parameter must be set to On. This will open the Remote GFDI

by means of a motor drive.
If the Remote GFDI has been opened by a motor drive via the RemMntSvc parameter, the insulation monitoring device

will start measuring after the delay defined in the IsoMeasDly parameter has elapsed. This allows the insulation

monitoring device to determine the insulation resistance without interrupting the feed-in operation. If an insulation error is

present, this will only be taken into account at the end of the delay time.
Once the insulation monitoring process is complete, the parameter RemMntSvc should be set to Off, thus putting the

PV array into grounded operation.
If, after approximately five minutes, one of the errors 3501 ‒ Insulation error, 3504 ‒ Insulation error ignored,

or 3601 ‒ Warning insulation error is displayed, the insulation is defective. In this case, a qualified person will need

to check and, if necessary, repair the insulation and then acknowledge the error.

Type of insulation monitoring device used
The insulation monitoring device used is the A-ISOMETER iso-PV1685 device supplied by Bender GmbH & Co. KG.

3.7.4.3 Remote Soft Grounding and Insulation Monitoring Device

With the order option "Remote Soft Grounding and Insulation Monitoring", it is possible to detect any faults that have

occurred, to disable the grounding of the PV array and to check the insulation with the integrated insulation monitoring

device.
When the Remote Soft Grounding is closed, the PV array is grounded. In this state, the insulation resistance cannot be

determined.
If the Remote Soft Grounding triggers, initially a temporary error will be assumed and the Remote Soft Grounding will be

closed again by a relay after a defined delay. No external switch command is required to close the triggered Remote

Soft Grounding. The Sunny Central will switch back to feed-in operation after a defined delay.
In the default setting, the Sunny Central software will attempt to start the Remote Soft Grounding up to three times per day.
If the Remote Soft Grounding triggers on several consecutive days, the software will assume that a permanent insulation

error has occurred and the Sunny Central will no longer revert to operation. In this case, a qualified person will need to

check and, if necessary, repair the insulation and then acknowledge the error.
When the Remote Soft Grounding is open, the grounding connection is disabled. In this state, the insulation monitoring

device continuously measures the insulation resistance. In the operating state "MPP load operation", the insulation

resistance of the entire system, from the PV array to the MV transformer, will be measured. If the Sunny Central is in the

operating state "Grid monitoring", only the insulation resistance from the PV array to the Sunny Central will be measured.
Insulation monitoring should be performed in the operating state "MPP load operation" so that all sections of the

PV system are included in the insulation measurement.

Insulation Monitoring

To disable the grounding of the PV array, the RemMntSvc parameter must be set to On. The Remote Soft Grounding

will then be opened via a high-voltage relay.
If the Remote Soft Grounding has been opened by relay via the RemMntSvc parameter, the insulation monitoring device

will start measuring after the period defined by the IsoMeasDly parameter has elapsed. This allows the insulation

monitoring device to determine the insulation resistance without interrupting the feed-in operation. If an insulation error is

present, this will only be taken into account at the end of the delay time.
Once the insulation monitoring process is complete, the parameter RemMntSvc should be set to Off, thus putting the

PV array into grounded operation.
If, after approximately five minutes, one of the errors 3501 ‒ Insulation error, 3504 ‒ Insulation error ignored,

or 3601 ‒ Warning insulation error is displayed, the insulation is defective. In this case, a qualified person will need

to check and, if necessary, repair the insulation and then acknowledge the error.