12 parameters, 1 sunny central, 1 power limitation – SMA SC 500CP-10-JP User Manual

Page 90

Advertising
background image

12  Parameters

SMA Solar Technology AG

90

SCCP-JP-BA-A4-en-12

User Manual

12 Parameters

12.1 Sunny Central

12.1.1 Power Limitation

Name

Description

Value/range

Explanation

Default

value

Plimit*

Nominal device power

0 kW to 500 kW

SC 500CP-JP

500 kW

0 kW to 700 kW

SC 630CP-JP

700 kW

0 kW to 880 kW

SC 800CP.JP

880 kW

Pmax**

Limitation of the nominal

power of the Sunny

Central

0 kW to 500 kW

SC 500CP-JP

500 kW

0 kW to 700 kW

SC 630CP-JP

700 kW

0 kW to 880 kW

SC 800CP-JP

880 kW

P-WMod**

Specification of active

power limitation mode

Off

Limits active power to

Pmax

Off

WCtlCom

Limitation of active power

via an external control unit,

such as the Power Reducer

Box

WCnst

Manual limitation of active

power in kW (P-W) via

communication devices,

such as the SC-COM

WCnstNom

Manual limitation of active

power in % (P-WNom) via

communication devices,

such as the SC-COM

WCnstNomAnIn

Limitation of active power in

% at the analog input

P-W

Limitation of active

power in kW
The active power

cannot exceed Pmax.

0 kW to 1,000 kW

SC 500CP-JP

500 kW

0 kW to 1,000 kW

SC 630CP-JP

700 kW

0 kW to 1,000 kW

SC 800CP-JP

880 kW

P-WNom

Limitation of active

power in %

0% to 100%

100%

P-HzStr**

Starting point of

frequency control

50 Hz to 55 Hz

For 50 Hz grid

50.2 Hz

60 Hz to 65 Hz

For 60 Hz grid

60.2 Hz

P-HzStop**

End point of frequency

control

50 Hz to 55 Hz

For 50 Hz grid

50.05 Hz

60 Hz to 65 Hz

For 60 Hz grid

60.05 Hz

P-HzStopMin

Minimum frequency at

end point of frequency

control

0 Hz to 55 Hz

For 50 Hz grid

0 Hz

0 Hz to 65 Hz

For 60 Hz grid

0 Hz