10  Troubleshooting

SMA Solar Technology AG

82

SCCP-JP-BA-A4-en-12

User Manual

6441

Sensor error occurred during

measurement of the DC voltage.

30 s

30 s

• Contact the SMA Service Line.

6443

Unspecified error occurred in digital

signal processor.

30 s

30 s

x

6447

Self-test in inverter bridge failed

Q

Q

6448

Insulation monitoring yields

non-permitted values.

W

W

• Check insulation monitoring.

6451

Measured AC voltage from

Sunny Central is less than voltage

from utility grid.

W

W

• Contact the SMA Service Line.

6452

Measured AC voltage from

utility grid is less than voltage from

Sunny Central.

W

W

6453

AC voltage of grid limits monitoring

mismatched

W

W

6454

AC current mismatched

W

W

6455

AC voltage mismatched

W

W

6456

Pre-charging circuit of DC link

defective

W

W

6457

Capacitor self-test failed

Q

Q

6461

Insulation monitoring device has not

adopted threshold.

15 min 15 min

x

• Ensure that insulation

monitoring device and wiring

OK.

6501

Internal temperature in

Sunny Central too high

30 s

1 min

• Check function of fans.
• Clean fans.
• Clean clogged fan inlets and

ventilation plates.

6502

Temperature at inverter bridge too

high

30 s

1 min

6508

Outside temperature too high

30 s

1 min

6605

Fast stop tripped due to

overtemperature

30 s

1 min

• Contact the SMA Service Line.

7001

Cable break or short circuit at

Sunny Central temperature sensor

W

W

• Check wiring of temperature

sensor.

• Contact the SMA Service Line.

7002

W

W

7004

W

W

7006

W

W

7501

Interior fan defective

W

W

• Check function of fans.
• Clean fans.
• Clean clogged fan inlets and

ventilation plates.

7502

W

W

7503

Inverter bridge defective

W

W

7507

Motor-protective circuit-breaker of

fan has tripped.

W

W

Error no.

Explanation

Behavior of the

Sunny Central

Corrective measures

S 1

S 2

R