20 ma transmitter output, Open collector outputs – Precision Digital PD6730X User Manual

Page 13

Advertising
background image

PD6730X Vantageview Super Snooper Modbus Scanner

Instruction Manual

13

4-20 mA Transmitter Output

OUTPUT SOURCE

Modbus PV 1-16, math channel 1-4, rate/process, total, grand total, or disabled

SCALING RANGE

4.000 to 20.000 mA for any display range.

DISABLE

If disabled, the output will output 3.2 mA

CALIBRATION

Factory Calibrated: 0.0 to 1000.0 = 4-20 mA output

UNDERRANGE

Output Underrange: 3.8 mA

OVERRANGE

Display Overrange: 20.5 mA
Output Overrange: 20.5 mA

ACCURACY

± 0.05% span ± 0.004 mA

TEMPERATURE
DRIFT

0.08 µA/

C max from -40 to 75C ambient

EXTERNAL LOOP
POWER SUPPLY

30 VDC maximum

OUTPUT LOOP
RESISTANCE

Power supply

Minimum

Maximum

24 VDC

10

 750

30 VDC

100

 1100

Note: loop-powered backlight subtracts 150

from maximum resistance figures

above.

Open Collector Outputs

OUTPUT
ASSIGNMENT

Two open collector pulse outputs Out 1 and Out 2.
Individually programmable for Modbus PV, math channel, pulse rate, total, or
grand total alarms; Modbus PV, math channel, pulse rate, total, or grand total
pulse outputs; or retransmitting of pulse inputs; constant timed pulse output;
quadrature outputs (requires Out 1 and Out 2); or off.

RATING

Isolated open collector, off: 24 VDC max, on: <1 V @ 150 mA max

ALARM OUTPUT

Assign to Modbus PV 1-16, math channel 1-4, or rate for high or low alarm trip
point.
Assign to total or grand total for total or grand total alarms.

ALARM
DEADBAND

0-100% FS, user selectable

ALARM
ACKNOWLEDGE

Front panel SCAN/ENTER button resets output and screen indication.

PULSE OUTPUT
COUNT

The pulse output count (COUNT) is programmable from 0.000001 to 9999999.
PV and math channels generate a frequency equal to the PV or math value
divided by the Count value. Rate pulses are generated at a rate of one output
pulse per Count value. Total and grand total pulses are generated for every
total or grand total increment selected (e.g. Count value of 100 will generate
one pulse every time the total is incremented by 100 units).
Pulse rate retransmission outputs one to one for input pulses, up to maximum
output speed. Count is not used for retransmitting outputs.

PULSE OUTPUT
PULSE WIDTH

Unless otherwise stated, pulses are 50% duty cycle for required frequency.
A pulse rate retransmit output will generate 100 to 130 μs pulses at the falling
edge of every input pulse.

PULSE OUTPUT
MAXIMUM
FREQUENCY

5 kHz, pulse width at 50% duty cycle.
If the outputs exceed 5 kHz, the scanner will display pUlse OVERRNG

QUADRATURE
OUTPUT

Output set to quadrature will lag the other pulse output by 90° (1/4 duty cycle)
at output frequency. Minimum 1 Hz

TIMER OUTPUT

Programmable on and off time, repeating cycle. Minimum period 0.1 second,
maximum 100,000 seconds. Minimum pulse time 0.01 second, maximum
10,000 seconds.