PD6730X Vantageview Super Snooper Modbus Scanner

Instruction Manual

79

Manual or Automatic Total Reset Function (TOTAL)

For manual reset, select Total Reset (TOTAL) and press Enter. Use the Up arrow button to select Manual
(MAN) and press Enter. Then select whether manual reset will be enabled (ENABLE) or disabled (DISABLE)
using the Up arrow key. Press the Enter button to accept. Disabling reset will avoid inadvertent resets of
the total via the front reset button or external reset contact.
For automatic reset, select Total Reset (TOTAL) and press Enter. Use the Up arrow button to select
Automatic

(AUTO) and press Enter. Press Enter at Time Delay (T DELAY) and enter reset delay time in

seconds. Once the output alarm total set point is reached, the meter waits for a programmed amount of
time (T DELAY) and then resets the total to zero. To enter the Time Delay, see Setting Numeric Values on
page 24 for more information.
Press the Enter button, at any time, to accept a setting; otherwise press the Menu button to exit without
saving changes.

Total Alarm Time

The T DELAY parameter is used by the NPN open collector outputs when they are programmed as total
alarms. If Total Reset (T RESET) is programmed to AUTO the Time Delay (T DELAY) is the length of the
associated Out 1 or Out 2 total alarm prior to the total being reset to 0.
For information on programming the NPN open collector pulse outputs as total alarms, see Alarm Output
(ALARM) programming on page 70.

Manual or Automatic Grand Total Reset Function (GrTOTAL)

For manual reset, select Grand Total Reset (GrTOTAL) and press Enter. Use the Up arrow button to
select Manual (MAN) and press Enter. Then select whether manual reset will be enabled (ENABLE) or
disabled (DISABLE) using the Up arrow key. Press the Enter button to accept. Disabling reset will avoid
inadvertent resets of the grand total via the front reset button or external reset contact.
For automatic reset, select Grand Total Reset (GrTOTAL) and press Enter. Use the Up arrow button to
select Automatic (AUTO) and press Enter. Press Enter at Time Delay (T DELAY) and enter reset delay
time in seconds. Once the output alarm total set point is reached, the meter waits for a programmed
amount of time (T DELAY) and then resets the grand total to zero. To enter the Time Delay, see Setting
Numeric Values on page 24 for more information.
Press the Enter button, at any time, to accept a setting; otherwise press the Menu button to exit without
saving changes.

Grand Total Alarm Time

The T DELAY parameter is used by the NPN open collector outputs when they are programmed as total
alarms. If Grand Total Reset (GTRESET) is programmed to AUTO the Time Delay (T DELAY) is the length of
the associated Out 1 or Out 2 total alarm prior to the total being reset to 0.
For information on programming the NPN open collector pulse outputs as total alarms, see Alarm Output
(ALARM) programming on page 70.