PD6730X Vantageview Super Snooper Modbus Scanner

Instruction Manual

30

The following table shows the PD6730X setup to work with the MTS M-Series gauges.

Parameter

PD6730X

Description/Comment

Mode

Snooper

PV1

Enable

PV1 Slave ID

100

Flow Meter 1 Address

Function Code

03

Register PV1

40001

Flow Meter 1 Rate

Data Type

Long integer Binary, Signed

Byte Order

1234

PV2 Enable

PV2 Slave ID

200

Flow Mater 2 Address

Function Code

03

Register PV2

40001

Flow Meter 2 Rate

Data Type

Long integer Binary, Signed

Byte Order

1234

Snooper Mode Response Time

2.0 seconds

Default Value

Serial Communications

Scanner ID

246

Must be Unique on the Network

Baud

4600 bps

Must Match All Network Devices

Transmit Time Delay

50 ms

Parity

None, 1 Stop Bit

Must Match All Network Devices

Setup

Display

Top Display

PV, Tag, & Units

Show PV, Tag, and Units for Each Top PV

Bottom Display

PV, Tag, & Units

Show PV, Tag, and Units for Each Bottom PV

PV Setup

PV 1

Format

Top Display

Show PV 1 (Flow Meter 1 Rate) on Bottom Display

Tag

RATE 1

Indicates Flow Meter 1 Rate

Units

GPM

Indicates Gallons Per Minute

Display Decimal Point

1

Scale

Scaling for Rate

Input 1

00000

Display 1

0.0

Input 2

50000

Display 2

5000.0

PV 2

Format

Bottom Display

Show PV 2 (Flow Meter 2 Rate) on Bottom Display

Tag

RATE 2

Indicates Flow Meter 2 Rate

Units

GPM

Indicates Gallons Per Minute

Display Decimal Point

1

Scale

Scaling for Rate

Input 1

00000

Display 1

0.0

Input 2

50000

Display 2

5000.0