Precision Digital PD6730X User Manual

Page 75

Advertising
background image

PD6730X Vantageview Super Snooper Modbus Scanner

Instruction Manual

75

The available parameters for PAR1, PAR2, and PAR3 show above are detailed below.

PAR Selection

Parameter

Description

PV 1

Modbus PV1

The scaled PV1 value; PV2 to PV16 also selectable

CV 1

Math Channel CV1

The math channel CV1 value; CV2 to CV4 also selectable

RATE

Rate

The pulse rate display rate value

TOTAL

Total

The total display value

GrTOTAL

Grand Total

The grand total display value

ABS

Nested Absolute Value*

Abs(L2 PAR1)

SQRT

Nested Square Root*

√(L2 PAR1)

SUM

Nested Addition*

L2P1 + L2P2

DIF

Nested Difference*

L2P1 - L2P2

MULTI

Nested Multiplication *

L2P1 * L2P2

DIVIDE

Nested Division*

L2P1 / L2P2

DIFABS

Nested Absolute diff. *

Abs(L2P1 - L2 PAR2)

WAVG

Nested Weighted avg.*

((L2P1 – L2P2)* L2P3) + L2P2

DRAW

Nested Draw*

((L2P1 / L2P2) – 1) * L2P3

RATIO

Nested Ratio*

(L2P1 / L2P2) * L2P3

CONCEN

Nested Concentration*

L2P1 / (L2P1 + L2P2) * L2P3

CONST

Constant

Constant value of 0.0001 to 99999

NONE

None No

parameter.

*Selecting this math function as a parameter will enter into the setup for a Nested Math Function. These
parameters are not available for level 2 parameters used when setting up the nested math function.

Nested Math Functions

To create more complicated math functions, the first level parameters allow a math function to be
selected as the parameter. In this case, a second level of parameters is selected for the nested math
function. These level 2 parameters are level 2 parameter 1, L2P1 (L2P1); level 2 parameter 2, L2P2
(L2P2); level 2 parameter 3, and L2P3 (L2P3). Level 2 parameters are selected similarly to other math
parameters; however additional nested math functions are unavailable for selection.

Entering a Constant Value

To enter a constant value, press Enter to select Constant (CONST). Value (VALUE) will display. Press
Enter

to confirm and enter a constant value. V.DP will display. Use the Up and Right arrows to select the

number of decimal points used in the constant value. Press Enter to select the number of decimal points
selected. Value will display. Set the constant value. See Setting Numeric Values on page 24 for more
information.

No Parameter (NONE)

Selecting a parameter of None will disable the math function. Any math function with a parameter of None
will display None (NONE) on the display as the value of the math function.

Gate Function (GATE)

The gate function is used for displaying slow pulse rates. Using the programmable gate, the meter is able
to display pulse rates as slow as 1 pulse every 9,999 seconds (0.0001 Hz). The gate function can also be
used to obtain a steady display reading with a fluctuating input signal.
There are two settings for the Gate, low gate (LO GaTE) and high gate (HI GATE).

Low Gate (LO GATE)

For most applications, low gate setting should be left at 1 second. Increase low gate setting to obtain a
steadier rate display. The rate display will update in accordance with the low gate setting, for example if
low gate is set at 10, the display will update every 10 seconds; changes in rate between updates will not
be reflected until next display update. The low gat may be set from 1 to 99 seconds.
To enter the Low Gate, press Enter to select Low Gate (LO GATE) and program the gate setting in
seconds. See Setting Numeric Values on page 24 for more information.