PD6730X Vantageview Super Snooper Modbus Scanner

Instruction Manual

29

Example 2: Snooper Displaying Flow Rate from Modbus Flow Meters

In this application we have a system consisting of (2) Modbus enabled flow meters connected to a
SCADA system operated out of a control room. A Modbus PLC polls the data out of the flow meters. A
PD6730-AX0-I-2 has been added to the system as a Modbus Snooper, to provide the operators an easy
to read field display near the flow lines.
The scanner displays one flow rate on the top display, and one on the bottom display. Each has an
alternating tag and unit for clear identification.

Example 2 Flow Meter & PLC Setup, Register Numbers, & Process Variables

Serial Communications
Parameters

Flow Transmitter 1

Flow Transmitter 2

Control Room PLC

Address (Slave ID)

100

200

N/A

Baud Rate

4800 bps

4800 bps

4800 bps

Transmit Delay

50 ms

50 ms

50 ms

Parity

None, 1 Stop Bit

None, 1 Stop Bit

None, 1 Stop Bit

Fixed Serial Data
Parameters

Modbus Flow Meter Data

Flow Data Register

30001, 30002

Data Type

Long Integer (2 registers), Binary, Signed

Byte Order

1234 (most significant digit register first)