APPLICATION EXAMPLES

The following applications show how the scanner can be configured for common applications.

Example 1: Master Polling Multivariable Level Transmitters

In this application we have a system consisting of (4) MTS M-Series multivariable tank level gauges
connected to PD6730-AX0-I-2 displaying product level, interface level, and average temperature. The
PD6730X is setup for Master mode, and is polling the Modbus transmitters.
Note: As a tank level indicator displaying in units of feet, a PD6730-AX0-I-L could also be considered for
this application. This would display feet and inches in the upper display, and include a tank level indicator.

Example 1 Level Transmitter Setup, Register Numbers, & Process Variables

Serial Communications
Parameters

Tank 1
Transmitter

Tank 2
Transmitter

Tank 3
Transmitter

Tank 4
Transmitter

Address (Slave ID)

001

002

003 004

Baud Rate

4800 bps

4800 bps

4800 bps

4800 bps

Transmit Delay

50 ms

50 ms

50 ms

50 ms

Parity

None 1

None 1

None 1

None 1

Fixed Serial Data
Parameters

MTS M-Series Transmitter Data

Level Register

30001, 30002

Interface Register

30003, 30004

Ave Temp Register

30017, 30018

Data Type

Long Integer (2 registers), Binary, Signed

Byte Order

1234 (most significant digit register first)

The following table shows the PD6730X setup to work with the MTS M-Series gauges.