Mailbox Messaging

MVI69-PDPMV1 ♦ CompactLogix or MicroLogix Platform

User Manual

PROFIBUS DPV1 Master

Page 100 of 225

ProSoft Technology, Inc.

July 8, 2011

4.4.6 Mailbox Message: Get Live List

This command returns 127 bytes of information about the nodes on the network.
Every byte stands for one bus subscriber, and the position of the byte in the
response data assigns the address (0 to 126), the content assigns the Station
Type.

This command can be sent in all operation modes (STOP, CLEAR, and
OPERATE), however the module must be initialized properly.

Parameter Description

Command Initiator

Application

Command Name

GET LIVE LIST

Command Number

1800h

Fragmented No

Extended Header Data

Fault information may be returned in the header of the response.

Command and Response Layout: Get Live List

Command

Response

Message ID

(ID)

(ID)

Message information

4002h

0002h

Command

0018h

0018h Get

Live

List

Data size

0000h

0007h

127 Bytes of Data

Frame count

0001h

0001h

Frame number

0001h

0001h

Offset high

0000h

0000h

Offset low

0000h

0000h

Extended word 1

-

-

Extended word 2

-

-

Extended word 3

-

-

Extended word 4

-

-

Extended word 5

-

-

Extended word 6

-

-

Extended word 7

-

Return Code

Extended word 8

-

Fault Information

Message Data byte 1

Station Type 0

Response Data Byte 1

Message Data byte 2

Station Type 1

Response Data Byte 1

Message Data byte 3

Station Type 2

Response Data Byte 1

...

...

Response Data Byte 1

Message Data byte "n"

Station Type 126

Response Data Byte 1