ProSoft Technology MVI69-PDPMV1 User Manual

Page 83

Advertising
background image

MVI69-PDPMV1 ♦ CompactLogix or MicroLogix Platform

Mailbox Messaging

PROFIBUS DPV1 Master

User Manual

ProSoft Technology, Inc.

Page 83 of 225

July 8, 2011

4.2

Sending a Mailbox Message in RSLogix 5000

Note: For this procedure, you must connect a serial cable from the serial port on your PC to the
DB9M connector on the CompactLogix or MicroLogix processor.

1 Open the sample ladder logic in RSLogix 5000.
2 Open the C

OMMUNICATIONS

menu, and choose G

O

O

NLINE

.

3 In the Controller Organization window, double-click C

ONTROLLER

T

AGS

.

4 Expand the MVI69PDPMV1 and MVI69PDPMV1.[Mailbox]Command tags.
5 Enter [1] (number one) in the tag

MVI69PDPMV1.[Mailbox]Command.GetLiveList, and then press [E

NTER

] to

send the mailbox message from the processor to the MVI69-PDPMV1.

6 Next, expand the tag MVI69PDPMV1.Mailbox.GetLiveList.Station, to verify

that the MVI69-PDPMV1 responded to the GetLiveList message.

For MVI69PDPMV1.Mailbox.GetLiveList.Station[1] (the PROFIBUS Master
Address), notice that the value has changed from 4 (not communicating) to 3
(Master).

For MVI69PDPMV1.Mailbox.GetLiveList.Station[125] (the PROFIBUS Slave
Address configured in the Slave Configuration procedure), notice that the
value has changed from 4 (not communicating) to 0 (Slave OK)