ProSoft Technology MVI69-PDPMV1 User Manual

Page 172

Advertising
background image

Reference MVI69-PDPMV1

♦ CompactLogix or MicroLogix Platform

User Manual

PROFIBUS DPV1 Master

Page 172 of 225

ProSoft Technology, Inc.

July 8, 2011

Byte Offset

Start End Name

Description

79 79 PROFIBUS Master

Operating State

PROFIBUS Master operating state
0x0000=Offline
0x4000=Stop
0x8000=Clear
0xC000=Operate

80 81 PROFIBUS Ident

Number

PROFIBUS Master PNO Ident number. Bytes will be
swapped

82 85 PROFIBUS Master

Serial Number

Unique 32-bit serial number for the PROFIBUS
Master

86 87 PROFIBUS

Software Version

Software version number for the PROFIBUS Master
software. Example for Version 1.40
High Byte - 0x40
Low Byte - 0x01

88 89 PROFIBUS Master

Module Status

Represents the PROFIBUS Master module's
operating status.
Bit 2=Application Status
0 - Application Stopped
1 - Application Running
Bit 8=data exchange (FBRS)
0 - There is no data exchange with any of the
assigned slaves
1 - There is Data Exchange with at least one of the
assigned slaves
Bit 9=slave input frozen/cleared (FBFC)
0 - A slaves inputs in the IN area are cleared in a
slave is not in Data Exchange
1 - A slave's inputs in the IN area are frozen if a
slave is not in Data Exchange
Bit 12=reset (RDR)
0 - No action
1 - A reset is requested by the PROFIBUS Master
module because a new database has been
downloaded

90 93 PROFIBUS

configuration
checksum

CRC32 checksum for PROFIBUS Master
configuration downloaded from configuration utility

94 97 MVI69 Module

configuration
checksum

MVI69-PDPMV1 module configuration checksum for
module configuration downloaded from configuration
utility

98 99 Application

program scan
counter

MVI69-PDPMV1 module program scan counter. Can
be used to gauge application code scan time
performance

100 101 Module PROFIBUS

output image data
update counter

Counter representing the number of times the output
data image is transferred to the module's internal
Master.

102 103 Module PROFIBUS

input image data
update counter

Counter representing the number of times the input
data image is transferred from the module's internal
Master.

104 105 Module out mailbox

counter

Module out mailbox counter

106 107 Module in mailbox

counter

Module in mailbox counter