6.3.4 MVI69 Input and Output Data Blocks

The following illustration shows how data, mailbox block, and status data is
transferred between the MVI69-PDPMV1 and the CompactLogix processor.

The blocks transferred between the module and the processor can perform
different tasks, according to the Block ID numbers.

MVI69 Input Data Block

This block contains the PROFIBUS cyclic input data received from the slaves.

240 Words Input Data Block Format (Input Image)

Word Offset

Start End Name

Description

0

0

Block ID

Block number 1 to 4

1 1 Output

Index

Index of Output image to receive (1 to 4 for data, 0 or
-1 if no data)

2

201

Input Data

PROFIBUS Input Data

202

202

Last Out Mailbox ID Last out mailbox message ID processed from output

image

203

203

Last In Mailbox ID

Last in mailbox message ID sent in input image

204

204

Last Alarm ID

Last alarm message ID sent in input image

205

205

Reserved

Reserved for future use

206

207

PROFIBUS CRC

PROFIBUS CRC32 value

208

209

Module CRC

Module CRC32 value

210

241