ProSoft Technology MVI69-PDPMV1 User Manual

Page 95

Advertising
background image

MVI69-PDPMV1 ♦ CompactLogix or MicroLogix Platform

Mailbox Messaging

PROFIBUS DPV1 Master

User Manual

ProSoft Technology, Inc.

Page 95 of 225

July 8, 2011

Message Information
Refer to Message Information (page 128).

Slave Address
Range 1 to 125; specifies the slave from which to read diagnostics.

Type of request
00h:
Internal slave diagnostic request. Returns the diagnostic information stored
in the Master. Can only be requested for slaves configured by the Master.

01h: External slave diagnostic request. Sends a diagnostic request on the
network to the specified slave. Can be requested for all slaves on the network.

Error code [1 ...4]
If "Return Code" equals 8030h ("Negative indication from lower layer"), status
values according to the DP-specification may be available in "Error Code 1".
Error Codes 2 to 4 are reserved.

Refer to Mailbox Messaging Error Codes (page 128).

Return Code
Refer to Mailbox Messaging Error Codes (page 128)

Fault Information
If "Invalid Other" is returned in the Message Information word in the header of the
response, information about the fault can be found here.

0100h: Address out of range.

0200h: Incorrect "Type of request"

0A00h: Failed to read diagnostic data from slave. Refer to Return Codes (page
129) for additional fault information.

0B00h: Remote station failure. Refer to Return Codes (page 129) for additional
fault information.

FF00h: Module offline (not initialized or no valid database).

Station Status [1 ... 3]
Refer to EN50170 Vol. 2 for more information.

Master Address
Address of the Master that parameterized the slave.

Ident Number
Unique ID assigned by the PROFIBUS User Organization.

Extended Diagnostic Data
Slave user-specific data. Refer to the documentation for the actual slave for more
information.