5.2
Basic Troubleshooting Steps
1 Verify that the module is installed correctly, and is communicating with the
processor. Refer to Module Setup (page 45) for setup procedures.
2 Install the most current version of ProSoft Configuration Builder.
3 Note the color and behavior of the LED Status Indicators (lights) on the front
panel. Refer to the chart in the following section for examples.
Special Note - Transferring Configuration Data to Replacement Module
All module configuration data (including MVI69 and PROFIBUS Network) are
stored on the Compact Flash in the MVI69 module. If a module failure occurs,
transfer the configuration data to the new module by moving the Compact Flash
from the old module to the replacement module.