ProSoft Technology MVI69-PDPMV1 User Manual

Page 118

Advertising
background image

Mailbox Messaging

MVI69-PDPMV1 ♦ CompactLogix or MicroLogix Platform

User Manual

PROFIBUS DPV1 Master

Page 118 of 225

ProSoft Technology, Inc.

July 8, 2011

4.4.13 Mailbox Message: Class 2 Acyclic Data Write

This command issues a Class 2 DPV1 acyclic write request to a slave. Prior to
issuing this command, a connection to the slave must have been established,
see Initiate Class 2 Connection (page 110).

Parameter Description

Command Initiator

Application

Command Name

FB_APPL_MSAC2_WRITE

Command Number

0028h

Fragmented No

Command and Response Layout: Class 2 Acyclic Write

Command

Response

Message ID

(ID)

(ID)

Message information

4002h

0002h

Command

0028h

0028h

Class 2 Acyclic Write

Data size

(data size)

(data size)

Number of data bytes (n)

Frame count

0001h

0001h

Frame number

0001h

0001h

Offset high

0000h

0000h

Offset low

0000h

0000h

Extended word 1

C_REF C_REF

Extended word 2

Slot

Index Slot

Index

Extended word 3

Length

-

Length

-

Extended word 4

-

-

Extended word 5

-

Error

Decode

Extended word 6

-

Error Code 1 Error Code 2

Extended word 7

-

Extended Fault information

Extended word 8

-

Fault Information

Message Data byte 1

Write Data

Write Data

Response Data byte 1

Message Data byte 2

Response Data byte 2

Message Data byte 3

Response Data byte 3

---

...

Message Data byte (n)

Response Data byte n