ProSoft Technology MVI69-PDPMV1 User Manual
Page 42

Ladder Logic
MVI69-PDPMV1 ♦ CompactLogix or MicroLogix Platform
User Manual
PROFIBUS DPV1 Master
Page 42 of 225
ProSoft Technology, Inc.
July 8, 2011
5 Click N
EXT
to continue.
6 Select the Requested Packet Interval value for scanning the I/O on the
module. This value represents the minimum frequency at which the module
will handle scheduled events. It should not be set to less than 1 millisecond.
Values between 5 and 10 milliseconds should work with most applications.
7 S
AVE
the module. Click OK to dismiss the dialog box. The Controller
Organization window now displays the module's presence. The following
illustration shows the Controller Organization window:
8 Copy the user-defined data types from the sample program.
9 Copy the controller tags from the sample program.
10 Copy the ladder rungs from the sample program.
11 Save and download (page 36) the new application to the controller and place
it in RUN mode.