MVI69 Output Data Block

This block contains the PROFIBUS cyclic output data to be sent from the
processor to the module and to the PROFIBUS slaves on the network.

240 Words Output Data Block Format (Output Image)

Word Offset

Start End Name

Description

0

0

Block ID

Block number 1 to 4

1 200

Output

Data

PROFIBUS Output Data

201

201

Last Out Mailbox ID Last out mailbox message ID sent through output

image

202

202

Last In Mailbox ID

Last in mailbox message ID processed from input
image

203

203

Last Alarm ID

Last alarm message ID processed from input image

204

205

PROFIBUS CRC

PROFIBUS CRC32 value

206

207

Module CRC

Module CRC32 value

208

240

Reserved

Reserved for future use

120 Words Output Data Block Format (Output Image)

Word Offset

Start End Name

Description

0

0

Block ID

Block number 1 to 8

1

100

Output Data

PROFIBUS Output Data (100 words of data)

101

101

Last Out Mailbox ID Last out mailbox message ID sent through output

image

102

102

Last In Mailbox ID

Last in mailbox message ID processed from input
image

103

103

Last Alarm ID

Last alarm message ID processed from input image

104

105

PROFIBUS CRC

PROFIBUS CRC32 value

106

107

Module CRC

Module CRC32 value

108

120

Reserved

Reserved for future use