6.2 PROFIBUS

DP

Architecture

The PROFIBUS DPV1 network supports multiple Master systems with several
slaves.

The most important features of PROFIBUS DPV1 are:

Standard

EIN 501 70
DIN 19245

Transmission Equipment
(Physical)

EIA RS-485
IEC 1158-2 (through link or coupler)
Fiber Optic Cable (not available)

Transfer Procedure

Half-duplex

Bus Topology

Linear bus with active bus termination

Bus Cable Type

Shielded twisted pair conductors

Connector 9-pin

D-Sub

Number of nodes on the bus

Max: 32 with no repeaters
Max: 125 with 3 repeaters in 4 segments

Effective Range

Max Bus Cable Length Per
Segment

Baud Rates (for 12 Mbit/sec cable)

1.2 km

9.6 kbps

1.2 km

19.2 kbps

1.2 km

93.75 kbps

1.0 km

187.5 kbps

0.5 km

500 kbps

0.2 km

1.5 Mbps

0.1 km

3 Mbps

0.1 km

8 Mbps

0.1 km

12 Mbps