background image

MVI69-PDPMV1 ♦ CompactLogix or MicroLogix Platform

Ladder Logic

PROFIBUS DPV1 Master

User Manual

ProSoft Technology, Inc.

Page 23 of 225

July 8, 2011

4 The following illustration shows an example where the module was

configured for a block transfer size of 60 words (input block size = 62 words,
output block size = 61 words):

Enter the Input Block Size and Output Block Size parameters according to
the Block Transfer Size to use:

Block Transfer Size

Input Block Size

Output Block Size

60 62 61

120 122 121

240 242 241

Important: You must set the Block Transfer Size in ProSoft Configuration Builder to match the
block size for the Add-On Instruction, otherwise the module may not function correctly.

5 On the C

ONNECTION

tab, check or un-check, as desired the Major fault option.