ProSoft Technology MVI69-PDPMV1 User Manual

Page 108

Advertising
background image

Mailbox Messaging

MVI69-PDPMV1 ♦ CompactLogix or MicroLogix Platform

User Manual

PROFIBUS DPV1 Master

Page 108 of 225

ProSoft Technology, Inc.

July 8, 2011

4.4.10 Mailbox Message: Class 1 Acyclic Data Write

This command initiates a DPV1 Class 1 acyclic write request. Refer to EN50170
(DPV1) for more information.

Parameter Description

Command Initiator

Application

Command Name

MSAC1 WRITE

Command Number

2100h

Fragmented No

Extended Header Data

Fault information may be returned in the header of the response.

Command and Response Layout: Acyclic Write

Command

Response

Message ID

(ID)

(ID)

Acyclic Message Status

Word

4002h

0002h

Command

0021h

0021h Acyclic

Write

Data size

(Size of data)

(Size of data)

Number of data bytes (n)

Frame count

0001h

0001h

Frame number

0001h

0001h

Offset high

0000h

0000h

Offset low

0000h

0000h

Extended word 1 Slave Addr. Slot Number

Slave Addr. Slot Number

Extended word 2

Index

Length Index

Length

Extended word 3

-

-

Extended word 4

-

-

Extended word 5

-

Error

Decode-

Extended word 6

-

Error Code 1 Error Code 2

Extended word 7

-

Extended Fault information

Extended word 8

-

Fault Information

Message Data byte 1

Data 1

Data 1

Message Data byte 2

Data 2

Data 2

Message Data byte 3

Data 3

Data 3

... ...

...

Message Data byte n

Data n

Data n

Advertising