background image

Mailbox Messaging

MVI69-PDPMV1 ♦ CompactLogix or MicroLogix Platform

User Manual

PROFIBUS DPV1 Master

Page 122 of 225

ProSoft Technology, Inc.

July 8, 2011

4.4.15 Mailbox Message: Class 2 Connection Abort Indication

This message is issued spontaneously by the module when any of the
established connections has been aborted for reasons not caused by the
application (e.g. slave time-out, connection terminated by slave etc.). This
message is not issued when a connection has been terminated using
FB_APPL_MSAC2_ABORT .

Note: The application must not respond to this message!
Note:This feature can be disabled, see “Fieldbus Specific Initialisation (FB_INIT)"

Parameter Description
Command Initiator

Module

Command Name

FB_APPL_MSAC2_ABORT_IND

Command Number

002Ah

Fragmented No

Message Layout:

Command

Message ID

(ID)

Message information

4002h

Command

002Ah FB_APPL_MSAC2_ABORT_IND

Data size

0000h

Frame count

0001h

Frame number

0001h

Offset high

0000h

Offset low

0000h

Extended word 1

C_REF

Extended word 2

Subnet

Reason

Code

Extended word 3

Additional Detail

Extended word 4

Locally Generated

Extended word 5

-

Extended word 6

-

Extended word 7

-

Extended word 8

-


C_REF
Connection reference number used to identify the connection.