MVI69-PDPMV1 ♦ CompactLogix or MicroLogix Platform

Module Setup

PROFIBUS DPV1 Master

User Manual

ProSoft Technology, Inc.

Page 65 of 225

July 8, 2011

6 Double click the slave icon to view the Slave Device properties.

In particular, note the following settings:

o

Automatic PROFIBUS Address Assignment:

ProSoft Configuration Builder automatically assigns a PROFIBUS address
to each new slave. The address assignment begins at address 3, and is
incremented by 1 for each new slave added to the network. You can
change the address in the Common tab of the Slave Properties dialog
box.

o

Automatic Input/Output Address Assignment:

For each new slave added to the PROFIBUS network, ProSoft
Configuration Builder automatically converts the input/output byte
addresses to word input/output addresses for the State RAM in the
processor.

7 Repeat steps 2 through 6 for all slaves you intend to place on the network.
8 When you are finished adding slaves, open the P

ROJECT

menu and choose

E

XIT

to return to the Master Setup dialog box.