Ladder Logic
MVI69-PDPMV1 ♦ CompactLogix or MicroLogix Platform
User Manual
PROFIBUS DPV1 Master
Page 22 of 225
ProSoft Technology, Inc.
July 8, 2011
2 Select 1769-MODULE.
3 Set the Module Properties values as follows:
Parameter Value
Name
Enter a module identification string. Example:
MVI69PDPMV1
Description
Enter a description for the module. Example: PROFIBUS
DPV1
M
ASTER
Comm Format
Select D
ATA
-INT
Slot
Enter the slot number in the rack where the MVI69-
PDPMV1 module will be installed.
Input Assembly Instance
101
Input Size
62 / 122 / 242
Output Assembly Instance
100
Output Size
61 / 121 / 241
Configuration Assembly Instance
102
Configuration Size
0