Standard PROFIBUS Slave Diagnostic Bytes

The diagnostic information consists of 6 bytes of standard diagnostic information
plus any user-related diagnostic information. The standard information is shown
in the tables below.

Byte Description

0

Station status 1

1

Station status 2

2

Station status 3

3 Master

address

4

Ident number high

5

Ident number low

5.6.1 Byte 0 - Station Status 1 Bits

Bit Description

0

Station not existent

1

Station not ready

2 Configuration

fault

3

Extended diagnostic data present

4 Not

supported

5

Invalid slave response

6 Parameter

fault

7 Master

lock

5.6.2 Byte 1 - Station Status 2 Bits

Bit Description

0 Parameter

request

1 Static

diagnostic

2 Slave

device

3 Watchdog

on

4 Freeze

mode

5 Sync

mode

6 Reserved

7 Slave

deactivated