The following table shows some of the possible status indicators.

Processor
Status

Module
Status

PROFIBUS Master
Status

PROFIBUS Master
Status LED Description

Normal
Operation

RUN (ON)

ACTIVE (ON)

COM STAT (GREEN):
Master is communicating
with all configured slaves.
DBASE STAT (GREEN):
PROFIBUS has been
configured.
TKN HOLD (GREEN):
Module is holding the
PROFIBUS token.
MSTR STAT (GREEN):
Master is in operating
mode.

PROFIBUS
Master is
stopped

RUN ACTIVE

COM STAT (OFF):
Master is not
communicating with
configured slaves.
DBASE STAT (GREEN):
PROFIBUS has been
configured.
TKN HOLD (GREEN):
Module is holding the
PROFIBUS token.
MSTR STAT (RED):
Master is in STOP mode.

CPU is in
Program
mode

PROG ACTIVE

COM STAT (OFF):
Master is not
communicating with
configured slaves.
DBASE STAT (GREEN):
PROFIBUS has been
configured.
TKN HOLD (GREEN):
Module is holding the
PROFIBUS token.
MSTR STAT (RED):
Master is in STOP mode.

CPU is in
Program
mode

PROG ACTIVE

COM STAT (OFF):
Master is operating but
there are no slaves
responding.
DBASE STAT (GREEN):
PROFIBUS has been
configured.
TKN HOLD (GREEN):
Module is holding the
PROFIBUS token.
MSTR STAT (GREEN):
Master is in operating
mode.

Advertising