120 Words Block Format for Mailbox In Message (Input Image)
When the Block Transfer Size = 120, it takes two Output blocks to form one
complete mailbox message request. Each Output block will be responded to with
a corresponding Input block with the same ID number.

Note: Since the same two Output Block IDs are always used for 120-word block format requests,
the Input Block IDs will always be the same two numbers, as well, 100 and 101.

Word Offset

Start End Name

Description

0

0

Block ID

Block number 100

1 1 Output

Index

Index of Output image to receive (1 to 8 for data, 0 or
-1 if no data)

2 121

Mailbox

Message

Mailbox input message from module (first 120 words
of mailbox message)

Word Offset

Start End Name

Description

0

0

Block ID

Block number 101

1 1 Output

Index

Index of Output image to receive (1 to 8 for data, 0 or
-1 if no data)

2 25 Mailbox

Message

Mailbox input message from module (last 24 words of
mailbox message)

26

121

Reserved

Reserved for future use