Chapter 3 Installing the TimeProvider

Making Connections

Expansion Panel
All connections to the Expansion Panel, including chassis ground, are made using
the interconnection cable.

Making Power Connections

To install the TimeProvider power connections:

1. Assemble a power connector appropriate for the type of shelf.

Table 3-1

lists the

pin-out for each type of connector.

Rear-access shelf: Crimp a No. 16 AWG (minimum) wire (1.31 mm

2

) to a spade

lug, then slide the spade lug under the terminal and tighten.

Front-access shelf: Assemble the power connector as shown in

Figure 3-6

.

Solder a No. 16 AWG (1.31 mm

2

) (minimum) wire to each pin. Slip the

appropriate grommet over the wires, and screw the shell together.

2. Attach the connector to the Power A and Power B connectors on the shelf.

Electrical Shock Caution: To avoid possible injury from shock,
make sure that the fuses are removed from the fuse panel or
power supply before connecting or applying power to the unit.

Warning: For continued fire protection, replace power supply
fuse(s) with the specified type and a 5 A rating. There are no
user-serviceable fuses in the TimeProvider shelf.

This unit must be grounded.

Refer all servicing to qualified personnel.

Table 3-1. Power Connections

Model 1100 Rear Access (NEBS) Shelf

Model 1000 Front Access (ETSI) Shelf

Signal

Terminal

Signal

Terminal

48 Volt Negative Lead

1

Frame Ground

1

48 Volt Positive Lead (return)

2

48 Volt Negative Lead

2

48 Volt Positive Lead (return)

3