-130-

22. SPECIFICATIONS

10

Option

1) Alarm outputs

Output types:

cAlarm point output d FAIL output e Chart
paper end (C.End) output

Numbers of outputs: RD200 … 6 points

RD2800 …6 or 12 points

Contact capacity (with resistive load):

cMOS relay output … 240 V (AC, DC), 50 mA (AC, DC)
d Mechanical relay (Common for “a” and “c” contacts) …

100VAC 0.5 A, 240VAC 0. 2A, 100VDC 0.3 A

Output wiring: AND/OR output selection is available for each

alarm points (including FAIL and C.End)

Relay coil phase: Energize/Not energize selectable*
Relay output latch: Hold/Not hold selectable*
Alarm display latch: Hold/Not hold selectable*

*Common to all relays

Dimension: The following length will be added for the depth.

RD200…14 mm (MOS relay, Mechanical “c”

contact)
25 mm (Mechanical “a” contact)

RD2800…16 mm (MOS relay, Mechanical “c”

contact)

27 mm (Mechanical “a” contact)

2) Remote contacts

Input terminals: 4 points (Common terminals: 2 points)
Input signal: Contact (Open/Shorted)
Voltage when the contact is open: Approx. 5 V
Current when the contact is shorted: Approx. 2 mA
Operations: Up to 4 input terminals can be selectable in the

following table.

Operation Terminal

c Printing ON/OFF, 3 chart speeds

2

d Message (No.1 to No.5) printing

4

e Message (No. 1 and No. 2) printing

2

f Digital data printing

1

g List 1 printing

1

h List 2 printing

1

i List 3 printing

1

j Operation record A

1

k Operation record B

1

l Operation record C

1

Operation record D

1

Reset of totalization*

1

*This operation is only available for the “totalization” (option).




3) Printing format

Trace printing format,

c Automatic range shift, d

Compressed/Expanded or

e Zone scale, is selectable for

each channel.. The format

e is common to all channels.

Automatic

range-shift

Printing area can be divided up to 5 ranges. It
switches the range according to the measured
values automatically for printing.

Compressed/

Expanded

Specific printing range is compressed or
expanded for printing.

Zone scale

Printing area is divided into 2 to 4 zones*. Data
of each channel is printed in the relevant zone.
*RD200 … 2, RD2800 … 2 to 4

4) Others

Options Detail

Communications

interface*

Specify one of the following modes.
RS-232C, RS-422A, RS-485

Input resistance

for current input*

Capable up to

±50mA DC by connecting an

input resistance to the measuring input
terminal.
100

Ω: Applicable current ±50mA

250

Ω: Applicable current ±20mA

Math

expression*

One of following math expressions is
selectable for each channel.
Addition, subtraction, multiplication, division,
natural logarithm, logarithm, exponential,
square root, temperature/humidity, maximum,
minimum, average value, absolute value,
data communications input*, flow rate
compensation.
*This function is only available for the
“communications interface” (option).

Totalizing*

Totalizing measured values and calculation
results. Reset function is executed with
programmed intervals or remote contacts
signals*.
*This function is only available for the
“remote contacts” (option).

Transmitter

power supply*

Power supply unit for the transmitter
generating input signal to the recorder

16 m chart paper

RD200 only …. Total chart paper length of
15.6 m

* Exclusive instruction manual is provided.

11

12