Caution – HT instruments SOLAR300N User Manual

Page 28

Advertising
background image

SOLAR300 - SOLAR300N

EN - 26

CAUTION

The Total Consumed Energy page is shown only if the instrument has been
set for the Recording of the General Parameter Total “Active Power &
Energy” (see § 5.4.2.7). Values will be shown only during or at the end of a
recording and zeroed upon starting a new recording or when the instrument
is switched off

25/01/2013 – 16:55:10

TOT. ENERGY PRODUCTION – Page x/y

Eact =

0

kWh

Ppeak =

0

kW

Date Ppeak

:

-- / -- / -- 00:00:00

Start rec.

:

-- / -- / -- 00:00:00

Stop rec.

:

-- / -- / -- 00:00:00

Rec Time

:

- - -

Int. Per.

:

- - -

Rec: - -

PAGE

SCOPE

HARM

VECTORS

PARAMETERS CAPTION:
Eact

 Total active energy produced when starting

recording.
Ppeak

 Maximum peak of produced active power.

Date Ppeak

 Date and time in which the peak occurred.

Start rec.

 Date when recording was started.

Stop rec.

 Date when recording was stopped.

Rec Time

 Time elapsed from Rec Start.

Int. Per.

 Value of the set integration period.

Rec

 Number of the recording in progress

Fig. 43: Producted energy page


CAUTION

The Total Produced Energy page is shown only if recording parameter “Co-
generation” has been set in the instrument (see § 5.4.2.5) and if general
parameter Total “Active Power & Energy” has been selected (see § 5.4.2.7).
Values will be shown only during or at the end of a recording and zeroed
upon starting a new recording or when the instrument is switched off.


5.2.4.3. 3-wire ARON three phase system – Screens sequence

12/09/2006 – 16:55:10

TOTAL RMS VALUES – Page x/y

V12

0.0

V23

0.0

V31

0.0

V

NEG%

0.0

ZERO%

0.0

SEQ

000

Hz

0.0

I1

0.0

I2

0.0

I3

0.0

A

PAGE

SCOPE

HARM

VECTORS

PARAMETERS CAPTION:
V12

 Phase L1 – Phase L2 voltage

V23

 Phase L2 – Phase L3 voltage

V23

 Phase L3 – Phase L1 voltage

NEG%

 Unbalance percentage of negative tern

ZERO%

 Unbalance percentage of zero tern

SEQ

 phases sequence indication as:

”123” = > Corrected
”132” = > Reversed
”023” = > Null voltage on the Black wire
”103” = > Null voltage on the Red wire
”120” = > Null voltage on the Brown wire
”100” = > Null voltage on the Red and Brown wires
”020” = > Null voltage on the Black and Brown wires
”003” = > Null voltage on the Black and Red wires
Hz

 Frequency

I1

 Current on L1 phase

I2

 Current on L2 phase

I3

 Current on L3 phase

Fig. 44: Page of numerical values