Caution, As tmodule_me tcel, 2rfv – HT instruments SOLAR300N User Manual

Page 50

Advertising
background image

SOLAR300 - SOLAR300N

EN - 48

5.3.2.6. Selection of the relationship for Temperature effects compensations
This option allows selecting the relationship to be used to correct the measurements
performed according to the modules’ temperature. The following correction modes are
available:

-

T.mod.:

Correction factor Rfv2 related to PV module Temp. (Italian guideline CEI-82-25)

-

T.env:

Correction factor Rfv2 related to environment Temp. (Italian guideline CEI-82-25)

-

ndc:

PRp (Performance ratio for active power) corrected by PV module Temp.

CAUTION

When performing test according to Italian guideline it is recommended to select
“T.env.”

Corr.

Type

Temperature (Tcel)

PRp calculation

Ref.

T.mod.

as

Tmodule_Me

Tcel



C)

40

Tcel

(if

100

40)

-

(Tcel

-

1

C)

40

Tcel

(if

1

fv2

R

n

STC

p

ca

P

G

G

Rfv

P

PRp

2

CEI

82-25

T.amb.





800

Irr

20

Tamb

Tcel

NOCT

dc

as

Tmodule_Me

Tcel

n

ca

cel

p

STC

P

P

T

G

G

PRp



25

100

1

- - -



where:

Symbol Description Meas.

unit

p

G

Irradiance on PV module surface

2

W/m

STC

G

Standard Irradiance = 1000

2

W/m

n

P

Nominal Power = sum of all power module (Pmax ) included in the part of PV plant
under test

 

kW

ca

P

AC Active Power measured

 

kW

2

Rfv

Thermal Coefficient factor

Absolute value of Pmax thermal coefficient

C

%/

NOCT

Normal Operating Cell Temperature (@ 800W/m

2

, 20°C, AM=1.5, Air speed =1m/s).

C

%/


For further details see § 10.1